Pipes and fittings thermally insulated with foamed polyurethane for domestic hot water transmission networks and heating networks

"Termo-Izol" Ltd.  is a domestic producer of thermally insulated pipes and pipeline components.
The pipes meet the requirements of PN EN 253

 

 


Thermal conductivity coefficient λ50 = 0.027 W / mK

 

Characteristics:

  • Temperature of the heat carrier up to 140 ° С, short-term temperature (240 hours per year) - up to 150 ° С
  • Maximum working pressure not greater than 2.5 MPa
  • Thermal insulation: polyurethane foam, foamed with cyclopentane
  • Waterproof polyethylene coating
  • Spiro coating - thin-walled sheet that is not subject to corrosion (above-ground installation)

Advantages

  • Reduction of heat losses during transport by 15-20%
  • The service life of hot water and district heating networks is 30-40 years
  • Reduction of investment outlays by 15-20%
  • 9-fold reduction in operating costs
  • 3-fold reduction in repair costs

Product nomenclature

  • pipes DN 32/90 - 1020/1200 mm, thermally pre-insulated with cyclopentane-foamed polyurethane foam, with a protective cover made of polyethylene or thin sheet metal (SPIRO) for domestic hot water networks and underground and above-ground heating networks;
  • elbows with a bend angle of 15 °, 30 °, 45 °, 60 °, 75 °, 90 ° (standard, extended, with venting connection); reductions (ordinary, eccentric);
  • U-shaped elements with compensating action;
  • tees (straight, angular, parallel);
  • supports (fixed, angular, sliding, guiding);
  • bellows expansion joints;
  • plugs (metal, metal with cable outlet, metal with signal cable outlet, polyethylene for pipes made of galvanized steel sheet);
  • end sleeves (separable, pre-formed);
  • fittings (shut-off valves, valves with one vent, valves with two vents, drains, valves with two drains);
  • adapters;
  • sealing rings;
  • sets for insulation of joints (ET-3 - heat shrinkable joints, ET-4 - joints for electric welding, ET-1 - joints made of galvanized steel sheet);
  • compensation pillows;
  • sliding tape;
  • alarm system (components for connectors, auxiliary tools, instruments).


 

 

Pipes and components for pre-insulated heating network pipelines are certified by Euroheat & Power.
Series of insulation of heat-insulated pipes
Conductive steel pipe with a PE protective sheath

 


Dn - nominal diameter of the conductive steel pipe
dz - outer diameter of the steel conductive pipe
Dz - outer diameter of the polyethylene protective coating

 

Conductive steel pipe in a protective metal sheath

 